Product overview
• This type of controller is applicable to the environment of three-phase four-wire auxiliary power supply. lts rated insulation voltage is 800V, which is suitable for infrequent conversion and infrequent motor starting in circuits with AC 50Hz, rated working voltage up to 690V and rated current up to 1250A.The circuit breaker has overvoltage protection, undervoltage protection, phase loss protection, overload long delay inverse time limit, short circuit short delay inverse time limit, shortcircuit short delay definite time limit, short circuit instantaneous and undervoltage protection, and leakage tripping protection functions,which can protect the line and power equipment from damage.
• The product complies with the following standards: GB 14048.2,DL/T2018 Molded Case Circuit Breaker Communication Protocol
• It passed the acceptance test of Jiangsu Electric Power Research Institute of the State Grid.
• It passed the communication test consistency test of the protocol laboratory of Jiangsu Electric Power Research Institute of China.
Protection function:
• With overvoltage, undervoltage and phase loss protection functions;Electronic overload,short circuitshort time delay, instantaneous protection and leakage tripping protection functions; And powerfailure tripping function.
Display function:
• 12864 dot matrix LCD display, friendly Chinese human-computer interface.
• Under the closing state, the current three-phase voltage, three-phase current, residual current, currenttime and rated current parameters will be displayed automatically.
• In the opening state,the current trip information is frozen and displayed.
Setting and query functions:
• Enable, alarm and disable the overvoltage, undervoltage, phase loss, overload, residual current, open circuit delay and instantaneous protection functions by pressing the key.The above functions can also be set through communication.
• Key can be used to set the main parameters such as overvoltage, undervoltage, phase loss, residual current, rated current, short circuit short delay multiple, short circuit short delay time, short circuit instantaneous multiple, real-time clock and user password.
• You can query, trip records, trip times, and many other parameters by pressing keys.
Control function:
• lt can be controlled through remote reservation opening, closing and self-inspection, as well as reservation cancellation.
• The synchronous opening function of the circuit breaker can be realized through the external opening interface.
Monitoring and recording function:
• Record the three-phase voltage, the three-phase current daily maximum value and time scale, and minimum value and time scale in the last 30 days, with 12 records in total.
• Record nearly 10 times of circuit breaker action events, gate status change events, circuit breaker alarm events, high-voltage side power failure events, and function on/off events
• Accumulate the number of protection trips and record the number of different fault trips.
Auxiliary functions:
• The RS485 communication function fully complies with the protocol requirements of the version of Communication Protocol for Molded Case Circuit Breakers (without leakage) issued by Jiangsu Province in 2018, as well as the requirements of the General Technical Specification for Molded Case Circuit Breakers and the Special Technical Specification for Molded Case Circuit Breakers issued by Jiangsu Province in 2018.
• Highlight LCD screen and four buttons to realize field operations such as function setting, parameter setting, gate position information query, trip times query, factory maintenance, etc. The remote upgrade function is realized through RS485 communication port. The upgrade mode meets the requirements of communication protocol of molded case circuit breaker of Jiangsu Electric Power Company.
Performance and process
• The circuit board is made of highly integrated industrial materials and adopts advanced lightning protection design, which fully meets the requirements of electromagnetic compatibility in GB14048.2-2008 standard
• The circuit board adopts compact structure design, which is suitable forusers’ requirements for compact space in the circuit breaker.
• The process of the circuit board is neat and beautiful, and the wiring is convenient. Only necessary signal input wiring is required.
• It can be directly assembled without secondary commissioning.After assembly, simply calibrate the voltage and current by pressing the button.
• The product basically includes the functions of current electronic molded case circuit breaker products.
• It can be designed and developed according to the structure (or original circuit board) of the customer’s prototype according to the customer’s requirements.
Normal working conditions
• Ambient temperature-5℃~+55°C;
• When the average minimum temperature of the wettest month of relative air humidity does not exceed 25℃, the monthly average maximum relative humidity of the month does not exceed 90%, taking into account the condensation on the product surface due to temperature changes;
• The altitude does not exceed 2,000 meters;
• Pollution level Ⅲ
• Installation category Ⅲ;
• The external magnetic field of the installation site shall not exceed 5 times of the geomagnetic field in any direction.
Technical parameters
Model specification | ZQM1EL-250 | ZQM1EL-400 | ZQM1EL-800 | ||||
Shell frame current | 250A | 400A | 800A | ||||
Rated current | 100~250A | 200~400A | 630~800A | ||||
Rated working voltage | |||||||
Rated insulation voltage | |||||||
Number of poles (p) | 3 | 4 | 3 | 4 | 3 | 4 | |
Breaking capacity grade | Icu(kA) | 50 | 50 | 85 | 85 | 85 | 85 |
lcs(kA) | 35 | 35 | 55 | 55 | 55 | 55 | |
Icw(kA/s) | 2.7/0.4 | 2.7/0.4 | 5/1 | 5/1 | 10/1 | 10/1 | |
Use category | A | B | B | ||||
Operatiing performance (times) | Power on | 1000 | 1000 | 500 | |||
No electricity | 7000 | 4000 | 2500 |
Main performance indicators of controller
Model | Description of parameter |
Rated current of shell frame grade Inm(A) | 60,250,400,630,800 optional |
Rated current In(A) | 0.4-1.0Inm(A)continuously adjustable |
Overload delay time (s) | 3-18s adjustable |
Short circuit short delay multiple (xln) | 2-12 adjustable |
Short circuit short delay time (ms) | 30-600 continuously adjustable |
Short circuot instantaneous multiple(xIn) | 4-14Adjustable |
Auxiliary power supply voltage Ue(AC V) | 400 |
Applicable pole number | 4P or 3P+N |
Overvoltage action value (v) | Default 285±5%(user adjustable) |
Undervoltage action value (v) | Default 165±5%(user adjustable) |
Phase loss action value (v) | Default120±5%(user adjustable) |
Product use category | Class B |
Rated residual operating current(mA) I △ n: | Gear values optional,and 8 groups of parameter values can be customized according to customer requirements. |
Rated residual non-operating current (mA)) | l △no=50% l △n |
Rated limit non-driving time (s) | Gear values optional and 3 groups of parameter values can be customized according to customer requirements. |