CJX2-F Ac contactor

• CJX2-F series AC contactor (hereinafter referred to as contactor) is applicable to 50Hz or 60HZ, equipped with special coil, can be used in circuits with 40~400AC, working voltage up to 660V, and working current up to 630A, for connection and disconnection of main circuit, and for frequent starting and control of motor; It can be used together with various relays and other general electrical equipment for various electrical equipment, motors and circuit control.

Product overview

• CJX2-F series AC contactor (hereinafter referred to as contactor) is applicable to 50Hz or 60HZ, equipped with special coil, can be used in circuits with 40~400AC, working voltage up to 660V, and working current up to 630A, for connection and disconnection of main circuit, and for frequent starting and control of motor; It can be used together with various relays and other general electrical equipment for various electrical equipment, motors and circuit control.
• It can also be combined with auxiliary contact group, air delay head and mechanical interlock to form mechanical interlock contactor and star delta starter, and can also be combined with thermal relay to form magnetic starter. Compliance standard: IEC60947-4-1 GB/T 14048.4.

 

Model meaning

CJX 2 – F □

CJX -Ac contactor
2 -Design serial number
F -Series code
□ -Rated working current

 

Structural features

Exquisite and compact structure, modular function, block assembly three-dimensional layout. The contactor is protective type, the action mechanism is direct-acting type, and the contact is double-break point. A mechanical interlocking mechanism can be added between the two contactors to form a mechanical interlocking (reversible conversion contactor) contactor.

 

Main technical parameters

Model CJX2
-F115
CJX2
-F150
ZCJX2
-F185
CJX2
-F205
CJX2
-F225
CJX2
-F265
CJX2
-F330
CJX2
-F400
CJX2
-F500
CJX2
-F630
Rated working current le(A) AC-3 380V 115 150 185 225 265 330 400 500 630
660V 86 107 118 135 170 325 305 355 460
AC-4 380V 52 60 79 85 105 217 138 147 188
660V 49 61 69 82 98 118 135 145 170
Maximum power of
controllable three-phase
squirrel-cage motor pe (kW)
AC-3 380V 55 75 90 110 132 160 200 250 335
660V 80 125 110 129 160 220 280 335 450
AC-4 380V 25 30 40 45 55 63 75 80 125
660V 45 55 63 75 90 110 129 140 160
Agreed heating current(lth) 200 250 275 315 350 450 500 700 1250
Rated working current (Ue) 380、660
Rated insulation voltage(Ui) 660
Meet a criterion IEC60947、GB14048
AC-3 Electrical life times 60×10⁴ 50×10⁴ 30×10⁴ 20×10⁴
Operating frequency 60° 30°
AC-4 Electrical life times 15×10⁴ 8×10⁴ 5×10⁴
Operating frequency 150 1×10⁵
Mechanical life Time 3×10⁵
Auxiliary contact Agreed heating
current (lth)
10
Electrical life times AC-15 60×10⁴ 50×10⁴ 30×10⁴ 20×10⁴
DC-13

 

CJX2-F115-330 appearance and installation dimensions

Product model Amax Bmax BImax Cmax G L P Q Q1 S X Z Y Fmin Kmin
CJX2-F115 165 164 137 167 80±0.8 108 37 29.5 60 15 57 26.5 M6×15 133 40
CJX2-F150 165 172 137 167 80±0.8 108 40 26.5 57.5 20 57 26.5 M6×20 133 40
CJX2-F185 171 176 137 181 80±0.8 114 40 30 60 20 59.5 29 M6×20 133 40
CJX2-F205
CJX2-F225 171 199 137 181 80±0.8 114 48 22 52 25 59.5 29 M6×30 133 40
CJX2-F265 204 205 145 210 96±1.1 143 48 39 66.5 25 61 44.5 M10×30 147 50
CJX2-F330 209 209 145 216 96±1.1 148 48 36 74 25 67 50.5 M10×30 147 60

Note: fmin is the space required to replace the coil, kmin is the minimum electrical distance, and the following is the same.

 

CJX2-F410 F500 appearance and installation dimensions

Product model Amax Bmax Cmax Fmin Kmin S J L P Q Q1
CJX2-F410 213 206 213 119 70 25 19.5 145 48 43 74
CJX2-F500 233 238 226 141 70 30 39.5 146 55 46 77