Product overview
• ZQB1 series high breaking miniature circuit breaker is applicable to lines with AC 50/60HZ, rated voltage 230/400V and rated current up to 63A for overload, short circuit and personal safety and equipment leakage protection.
• In addition, the electronic circuit design is advanced, the unique filtering device and chip mounting process, and the high anti-interference performance can effectively prevent the misoperation caused by the instantaneous voltage change and surge current. The circuit breaker is applicable to industrial, commercial, high-rise and civil buildings and similar places, and can also be used for infrequent on-off operations. Suitable for non-professional personnel.
• External accessories: alarm, auxiliary, shunt+auxiliary, undervoltage and overvoltage.
• Product function: overload and short circuit protection.
• Product use: for power distribution and lighting, and for motor protection.
• Number of product poles: 1,2,3,4.
• Breaking capacity: 6000A.
• Product current: 1, 3,6, 10,16, 20,25,32,40, 50,63A.
• Executive standards: IEC 60898-1,IEC 1259-1, GB/T10963.1GB/T16917.1.
Model and its meaning
ZQ B 1 – 63 / C 16 / 2P
ZQ -Name of the company
B -Product model
1 -Design serial number
63 -Shell frame grade current
C -Tripping characteristic
16 -Operating current (optional)
2P -Number of poles
Technical parameters
Rated current of shell frame grade Inm(A) | Number of poles | Rated voltage (V) | Rated voltage (V) | Rated current (A) | Rated operating short circuit breaking capability Ics | Rated limit short circuit breaking capacity Icu | ||
Breaking current(A) | COSφ | Breaking current(A) | COSφ | |||||
63 | 1 | 50 or 60 | 230、400 | 1.3 6.10 16.20 25.32 4.50 63 | 6000 | 0.7 | 6000 | 0.7 |
2 | 230、400 | |||||||
3 | 400 | |||||||
4 | 400 |
Serial number | Test current | Initial state | Tripping or non-tripping time limit | Expectec result | Remarks |
a | 1.13In | Cold state* | t≥1h (≤ 63A) | No tripping | |
b | 1.45In | Right after test A | t<1h (≤ 63A) | Tripping | The current rises steadily to the specified value within 5s. |
C | 2.55In | Cold state* | 1s<t<60s (In ≤ 32A) | Tripping | |
1s<t<120s (In > 32A) | |||||
d | 3In | Cold state * | t≥0.1s | Tripping | B |
5In | C | ||||
10In | D | ||||
e | 5In | Cold state* | t<0.1s | Tripping | B |
10In | C | ||||
15In | D |